Changes for page 8. Control Setup Manual
Last modified by Iaroslav Platonov on 2026/06/09 11:18
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -1,7 +1,5 @@ 1 1 = CONTENT = 2 2 3 -{{toc/}} 4 - 5 5 = 1. INTRODUCTION = 6 6 7 7 CENTO is a multifunctional software platform for data acquisition, processing and display. This manual describes how to configure the CENTO user tool Control. ... ... @@ -22,11 +22,11 @@ 22 22 23 23 **C** is an abbreviation for //Control//. **TC** is an abbreviation for Remote //control.// In CENTO software, //Control// refers to sending a non-negative integer value to a device, while Remote //control //refers to sending a discrete signal. 24 24 25 -[[image:Screenshot 2025-12-17 at 16.28.40.png ||height="441" width="1445"]]23 +[[image:Screenshot 2025-12-17 at 16.28.40.png]] 26 26 27 27 Figure 2.1. Tags with remote control enabled 28 28 29 -[[image:Screenshot 2025-12-17 at 16.29.26.png ||height="584" width="1424"]]27 +[[image:Screenshot 2025-12-17 at 16.29.26.png]] 30 30 31 31 Figure 2.2. Tags with control and remote control enabled 32 32 ... ... @@ -38,7 +38,7 @@ 38 38 39 39 To proceed, enter the account password. After successful authentication, a modal window appears allowing to specify the value to be written to the device (see Fig. 2.4). 40 40 41 -[[image:Screenshot 2025-12-17 at 16.31.55.png ||height="315" width="1392"]]39 +[[image:Screenshot 2025-12-17 at 16.31.55.png]] 42 42 43 43 Figure 2.4. Entering value for control 44 44 ... ... @@ -46,13 +46,13 @@ 46 46 47 47 Next, confirm the entered value by clicking **Execute** to initiate the control command and write the value to the device. Alternatively, click **Cancel,** to cancel the operation (see Fig. 2.5). 48 48 49 -[[image:Screenshot 2025-12-17 at 16.32.27.png ||height="313" width="1382"]]47 +[[image:Screenshot 2025-12-17 at 16.32.27.png]] 50 50 51 51 Figure 2.5. Confirmation of the command to write a value 52 52 53 53 Clicking **TC** also opens a password prompt window. After successful authentication, a command selection window appears (see Fig. 2.6). As with the Control, a confirmation window follows the selected command. 54 54 55 -[[image:Screenshot 2025-12-17 at 16.33.06.png ||height="263" width="1368"]]53 +[[image:Screenshot 2025-12-17 at 16.33.06.png]] 56 56 57 57 Figure 2.6. Selecting command for remote control 58 58 ... ... @@ -81,11 +81,11 @@ 81 81 82 82 In the Remote **control **field, select the appropriate ASDU type for the control command from the drop-down list (see Fig. 3.1.4). 83 83 84 -[[image:Screenshot 2025-12-17 at 16.38.45.png ||height="386" width="633"]]82 +[[image:Screenshot 2025-12-17 at 16.38.45.png]] 85 85 86 86 Figure 3.1.1. Setting remote control via Modbus protocol 87 87 88 -[[image:Screenshot 2025-12-17 at 16.39.12.png ||height="384" width="628"]]86 +[[image:Screenshot 2025-12-17 at 16.39.12.png]] 89 89 90 90 Figure 3.1.2. Setting remote control via IEC-104 protocol 91 91 ... ... @@ -109,11 +109,11 @@ 109 109 110 110 2) The //Control// function is available for Modbus TCP (Modbus RTU over TCP) protocols (see Fig. 3.1.3 ), and OPC DA (see Fig. 3.1.9). 111 111 112 -[[image:Screenshot 2025-12-17 at 16.40.14.png ||height="461" width="622"]]110 +[[image:Screenshot 2025-12-17 at 16.40.14.png]] 113 113 114 114 Figure 3.1.3. Setting control for Modbus protocol 115 115 116 -[[image:Screenshot 2025-12-17 at 16.41.11.png ||height="286" width="309"]]114 +[[image:Screenshot 2025-12-17 at 16.41.11.png]] 117 117 118 118 Figure 3.1.4. Remote control for IEC-104 119 119 ... ... @@ -123,7 +123,7 @@ 123 123 124 124 The **Function** field selects the Modbus recording function from the drop-down list (see Fig. 3.1.5). 125 125 126 -[[image:Screenshot 2025-12-17 at 16.41.51.png ||height="168" width="313"]]124 +[[image:Screenshot 2025-12-17 at 16.41.51.png]] 127 127 128 128 Figure 3.1.5. Modbus control function 129 129 ... ... @@ -135,29 +135,29 @@ 135 135 136 136 The field **Byte order** from the drop-down list (see Fig. 3.1.6) is used to select different order of bytes and/or words in the written CENTO data. 137 137 138 -[[image:Screenshot 2025-12-17 at 16.42.23.png ||height="198" width="319"]]136 +[[image:Screenshot 2025-12-17 at 16.42.23.png]] 139 139 140 140 In the **Device Tag Data Type** field, select the data type used by the device to store values from the drop-down list (see the device manual for details) (see Fig. 3.1.7). 141 141 142 -[[image:Screenshot 2025-12-17 at 16.43.58.png ||height="316" width="317"]]140 +[[image:Screenshot 2025-12-17 at 16.43.58.png]] 143 143 144 144 Fig. 3.1.7. Device Tag Data Type 145 145 146 146 In the **Transformation** block, a linear transformation is applied to convert a physical quantity into a value to be recorded, using defined upper and lower limits for both. These limits establish the valid ranges for the physical quantity and its corresponding recorded value, within which data can be filled in (see Fig. 3.1.8). 147 147 148 -[[image:Screenshot 2025-12-17 at 16.44.29.png ||height="149" width="530"]]146 +[[image:Screenshot 2025-12-17 at 16.44.29.png]] 149 149 150 150 Figure 3.1.8. Transformation block 151 151 152 152 In devices using the OPC DA protocol, the control function is easier to configure. In the settings, enable **Write values**, select the device tag data type, and define the necessary transformations (see Fig. 3.1.9). 153 153 154 -[[image:Screenshot 2025-12-17 at 16.45.36.png ||height="371" width="598"]]152 +[[image:Screenshot 2025-12-17 at 16.45.36.png]] 155 155 156 156 Figure 3.1.9. Configuring control for OPCDA protocol 157 157 158 158 == 3.2. Setting control using MS Excel == 159 159 160 -To configure **Control **for a tag polled via the required protocol using Excel, download a configuration template. To do this, navigate to Settings > Configuration files in the CENTO interface. The **Import/Export configuration file** page opens (see Fig. 3.2.1). In the **Tags and Channels** section, click** Download** to download the template file.158 +To configure **Control **for a tag polled via the required protocol using Excel, download a configuration template. To do this, navigate to Settings > Configuration files in the CENTO interface. The **Import/Export configuration file** page opens (see Fig. 3.2.1). In the **Tags and Channels** section, click** Download** to download the template file. 161 161 162 162 [[image:Screenshot 2025-12-17 at 16.50.31.png]] 163 163 ... ... @@ -165,9 +165,9 @@ 165 165 166 166 Next, open the previously downloaded file, which contains a list of all tags used in CENTO. The details for setting these tags are outlined in the corresponding manual for configuring tags and devices based on the selected protocol. 167 167 168 -[[image:Screenshot 2025-12-17 at 16.51.23.png ||height="261" width="950"]]166 +[[image:Screenshot 2025-12-17 at 16.51.23.png]] 169 169 170 -[[image:Screenshot 2025-12-17 at 16.51.40.png ||height="319" width="954"]]168 +[[image:Screenshot 2025-12-17 at 16.51.40.png]] 171 171 172 172 Figure. 3.2.2. Table of tags 173 173 ... ... @@ -227,7 +227,7 @@ 227 227 This class has four attributes to be specified exactly as shown in Figure 3.3.1: 228 228 229 229 * **Tag ID **is a mandatory field; 230 -* Optional fields include the lower and upper limits of values, which define the range within which any values can be entered. The **Value variants** field is provided for convenience, allowing to select from predefined options instead of manually entering values. To use this feature, specify a reference to the directory in the **Type** column, such as// ref_value_variants //(see Fig. 3.3.6). This reference can then be used to select the desired numeric parameters (see Fig. 3.3.7).228 +* Optional fields include the lower and upper limits of values, which define the range within which any values can be entered. The **Value variants** field is provided for convenience, allowing to select from predefined options instead of manually entering values. To use this feature, specify a reference to the directory in the **Type** column, such as// ref_value_variants //(see Fig. 3.3.6). This reference can then be used to select the desired numeric parameters (see Fig. 3.3.7). 231 231 232 232 Check the created //Write value// class on the classes editor page: 233 233 ... ... @@ -265,7 +265,7 @@ 265 265 266 266 Figure 3.3.7. Table of IM directories 267 267 268 -IM directories can also be configured using the web** Information Model editor** on the **Directories** tab. The directory shown in Fig. 3.3.7 is displayed in the web interface as illustrated in Fig. 3.3.8.266 +IM directories can also be configured using the web** Information Model editor** on the **Directories** tab. The directory shown in Fig. 3.3.7 is displayed in the web interface as illustrated in Fig. 3.3.8. 269 269 270 270 [[image:Screenshot 2025-12-17 at 16.58.31.png]] 271 271