Changes for page 8. Control Setup Manual
Last modified by Iaroslav Platonov on 2026/06/09 11:18
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 5 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -1,5 +1,7 @@ 1 1 = CONTENT = 2 2 3 +{{toc/}} 4 + 3 3 = 1. INTRODUCTION = 4 4 5 5 CENTO is a multifunctional software platform for data acquisition, processing and display. This manual describes how to configure the CENTO user tool Control. ... ... @@ -20,11 +20,11 @@ 20 20 21 21 **C** is an abbreviation for //Control//. **TC** is an abbreviation for Remote //control.// In CENTO software, //Control// refers to sending a non-negative integer value to a device, while Remote //control //refers to sending a discrete signal. 22 22 23 -[[image:Screenshot 2025-12-17 at 16.28.40.png]] 25 +[[image:Screenshot 2025-12-17 at 16.28.40.png||height="441" width="1445"]] 24 24 25 25 Figure 2.1. Tags with remote control enabled 26 26 27 -[[image:Screenshot 2025-12-17 at 16.29.26.png]] 29 +[[image:Screenshot 2025-12-17 at 16.29.26.png||height="584" width="1424"]] 28 28 29 29 Figure 2.2. Tags with control and remote control enabled 30 30 ... ... @@ -36,7 +36,7 @@ 36 36 37 37 To proceed, enter the account password. After successful authentication, a modal window appears allowing to specify the value to be written to the device (see Fig. 2.4). 38 38 39 -[[image:Screenshot 2025-12-17 at 16.31.55.png]] 41 +[[image:Screenshot 2025-12-17 at 16.31.55.png||height="315" width="1392"]] 40 40 41 41 Figure 2.4. Entering value for control 42 42 ... ... @@ -44,13 +44,13 @@ 44 44 45 45 Next, confirm the entered value by clicking **Execute** to initiate the control command and write the value to the device. Alternatively, click **Cancel,** to cancel the operation (see Fig. 2.5). 46 46 47 -[[image:Screenshot 2025-12-17 at 16.32.27.png]] 49 +[[image:Screenshot 2025-12-17 at 16.32.27.png||height="313" width="1382"]] 48 48 49 49 Figure 2.5. Confirmation of the command to write a value 50 50 51 51 Clicking **TC** also opens a password prompt window. After successful authentication, a command selection window appears (see Fig. 2.6). As with the Control, a confirmation window follows the selected command. 52 52 53 -[[image:Screenshot 2025-12-17 at 16.33.06.png]] 55 +[[image:Screenshot 2025-12-17 at 16.33.06.png||height="263" width="1368"]] 54 54 55 55 Figure 2.6. Selecting command for remote control 56 56 ... ... @@ -79,11 +79,11 @@ 79 79 80 80 In the Remote **control **field, select the appropriate ASDU type for the control command from the drop-down list (see Fig. 3.1.4). 81 81 82 -[[image:Screenshot 2025-12-17 at 16.38.45.png]] 84 +[[image:Screenshot 2025-12-17 at 16.38.45.png||height="386" width="633"]] 83 83 84 84 Figure 3.1.1. Setting remote control via Modbus protocol 85 85 86 -[[image:Screenshot 2025-12-17 at 16.39.12.png]] 88 +[[image:Screenshot 2025-12-17 at 16.39.12.png||height="384" width="628"]] 87 87 88 88 Figure 3.1.2. Setting remote control via IEC-104 protocol 89 89 ... ... @@ -107,11 +107,11 @@ 107 107 108 108 2) The //Control// function is available for Modbus TCP (Modbus RTU over TCP) protocols (see Fig. 3.1.3 ), and OPC DA (see Fig. 3.1.9). 109 109 110 -[[image:Screenshot 2025-12-17 at 16.40.14.png]] 112 +[[image:Screenshot 2025-12-17 at 16.40.14.png||height="461" width="622"]] 111 111 112 112 Figure 3.1.3. Setting control for Modbus protocol 113 113 114 -[[image:Screenshot 2025-12-17 at 16.41.11.png]] 116 +[[image:Screenshot 2025-12-17 at 16.41.11.png||height="286" width="309"]] 115 115 116 116 Figure 3.1.4. Remote control for IEC-104 117 117 ... ... @@ -121,7 +121,7 @@ 121 121 122 122 The **Function** field selects the Modbus recording function from the drop-down list (see Fig. 3.1.5). 123 123 124 -[[image:Screenshot 2025-12-17 at 16.41.51.png]] 126 +[[image:Screenshot 2025-12-17 at 16.41.51.png||height="168" width="313"]] 125 125 126 126 Figure 3.1.5. Modbus control function 127 127 ... ... @@ -133,29 +133,29 @@ 133 133 134 134 The field **Byte order** from the drop-down list (see Fig. 3.1.6) is used to select different order of bytes and/or words in the written CENTO data. 135 135 136 -[[image:Screenshot 2025-12-17 at 16.42.23.png]] 138 +[[image:Screenshot 2025-12-17 at 16.42.23.png||height="198" width="319"]] 137 137 138 138 In the **Device Tag Data Type** field, select the data type used by the device to store values from the drop-down list (see the device manual for details) (see Fig. 3.1.7). 139 139 140 -[[image:Screenshot 2025-12-17 at 16.43.58.png]] 142 +[[image:Screenshot 2025-12-17 at 16.43.58.png||height="316" width="317"]] 141 141 142 142 Fig. 3.1.7. Device Tag Data Type 143 143 144 144 In the **Transformation** block, a linear transformation is applied to convert a physical quantity into a value to be recorded, using defined upper and lower limits for both. These limits establish the valid ranges for the physical quantity and its corresponding recorded value, within which data can be filled in (see Fig. 3.1.8). 145 145 146 -[[image:Screenshot 2025-12-17 at 16.44.29.png]] 148 +[[image:Screenshot 2025-12-17 at 16.44.29.png||height="149" width="530"]] 147 147 148 148 Figure 3.1.8. Transformation block 149 149 150 150 In devices using the OPC DA protocol, the control function is easier to configure. In the settings, enable **Write values**, select the device tag data type, and define the necessary transformations (see Fig. 3.1.9). 151 151 152 -[[image:Screenshot 2025-12-17 at 16.45.36.png]] 154 +[[image:Screenshot 2025-12-17 at 16.45.36.png||height="371" width="598"]] 153 153 154 154 Figure 3.1.9. Configuring control for OPCDA protocol 155 155 156 156 == 3.2. Setting control using MS Excel == 157 157 158 -To configure **Control **for a tag polled via the required protocol using Excel, download a configuration template. To do this, navigate to Settings > Configuration files in the CENTO interface. The **Import/Export configuration file** page opens (see Fig. 3.2.1). In the **Tags and Channels** section, click** Download** to download the template file.160 +To configure **Control **for a tag polled via the required protocol using Excel, download a configuration template. To do this, navigate to Settings > Configuration files in the CENTO interface. The **Import/Export configuration file** page opens (see Fig. 3.2.1). In the **Tags and Channels** section, click** Download** to download the template file. 159 159 160 160 [[image:Screenshot 2025-12-17 at 16.50.31.png]] 161 161 ... ... @@ -163,9 +163,9 @@ 163 163 164 164 Next, open the previously downloaded file, which contains a list of all tags used in CENTO. The details for setting these tags are outlined in the corresponding manual for configuring tags and devices based on the selected protocol. 165 165 166 -[[image:Screenshot 2025-12-17 at 16.51.23.png]] 168 +[[image:Screenshot 2025-12-17 at 16.51.23.png||height="261" width="950"]] 167 167 168 -[[image:Screenshot 2025-12-17 at 16.51.40.png]] 170 +[[image:Screenshot 2025-12-17 at 16.51.40.png||height="319" width="954"]] 169 169 170 170 Figure. 3.2.2. Table of tags 171 171 ... ... @@ -225,7 +225,7 @@ 225 225 This class has four attributes to be specified exactly as shown in Figure 3.3.1: 226 226 227 227 * **Tag ID **is a mandatory field; 228 -* Optional fields include the lower and upper limits of values, which define the range within which any values can be entered. The **Value variants** field is provided for convenience, allowing to select from predefined options instead of manually entering values. To use this feature, specify a reference to the directory in the **Type** column, such as// ref_value_variants //(see Fig. 3.3.6). This reference can then be used to select the desired numeric parameters (see Fig. 3.3.7).230 +* Optional fields include the lower and upper limits of values, which define the range within which any values can be entered. The **Value variants** field is provided for convenience, allowing to select from predefined options instead of manually entering values. To use this feature, specify a reference to the directory in the **Type** column, such as// ref_value_variants //(see Fig. 3.3.6). This reference can then be used to select the desired numeric parameters (see Fig. 3.3.7). 229 229 230 230 Check the created //Write value// class on the classes editor page: 231 231 ... ... @@ -263,7 +263,7 @@ 263 263 264 264 Figure 3.3.7. Table of IM directories 265 265 266 -IM directories can also be configured using the web** Information Model editor** on the **Directories** tab. The directory shown in Fig. 3.3.7 is displayed in the web interface as illustrated in Fig. 3.3.8.268 +IM directories can also be configured using the web** Information Model editor** on the **Directories** tab. The directory shown in Fig. 3.3.7 is displayed in the web interface as illustrated in Fig. 3.3.8. 267 267 268 268 [[image:Screenshot 2025-12-17 at 16.58.31.png]] 269 269 ... ... @@ -392,3 +392,8 @@ 392 392 393 393 [[image:Screenshot 2025-12-17 at 17.38.57.png]] 394 394 397 +[[image:Screenshot 2025-12-17 at 17.42.19.png]] 398 + 399 +[[image:Screenshot 2025-12-17 at 17.41.38.png]] 400 + 401 +[[image:Screenshot 2025-12-17 at 17.42.37.png]]
- Screenshot 2025-12-17 at 17.40.05.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Lana - Size
-
... ... @@ -1,0 +1,1 @@ 1 +12.2 KB - Content
- Screenshot 2025-12-17 at 17.40.35.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Lana - Size
-
... ... @@ -1,0 +1,1 @@ 1 +57.7 KB - Content
- Screenshot 2025-12-17 at 17.41.38.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Lana - Size
-
... ... @@ -1,0 +1,1 @@ 1 +47.4 KB - Content
- Screenshot 2025-12-17 at 17.42.19.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Lana - Size
-
... ... @@ -1,0 +1,1 @@ 1 +56.7 KB - Content
- Screenshot 2025-12-17 at 17.42.37.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Lana - Size
-
... ... @@ -1,0 +1,1 @@ 1 +57.9 KB - Content