Changes for page 3. Metering Channels

Last modified by Iaroslav Platonov on 2026/06/08 09:57

From version 58.1
edited by Lana
on 2025/11/30 19:59
Change comment: There is no comment for this version
To version 60.1
edited by Lana
on 2025/12/03 20:29
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,16 +1,16 @@
1 -== CONTENT ==
1 += CONTENT =
2 2  
3 3  {{toc/}}
4 4  
5 -== 1. INTRODUCTION ==
5 += 1. INTRODUCTION =
6 6  
7 7  CENTO is a multifunctional software platform for data collection, processing, and display. This Guide contains a description of setting up metering of electricity, energy resources, as well as other types of metering.
8 8  
9 9  It is assumed that the user, having read the instructions "User manual" and "Setup manual", is already familiar with the main elements of the interface and how to configure CENTO.
10 10  
11 -== 2. ELECTRICITY METERING ==
11 += 2. ELECTRICITY METERING =
12 12  
13 -=== 2.1. Device setup ===
13 +== 2.1. Device setup ==
14 14  
15 15  CENTO software can work with a variety of metering devices that have the ability to measure and store power and power profiles. The metering function is enabled by adding the metering protocol corresponding to the device on the **Device editing** page (Settings > Devices, tags, channels > Devices), then, similar to other polling protocols, the parameters of communication with the device (RTU address, TCP/UDP port, timeout and number of connection attempts) and scheduled polling parameters (cron of CENTO rules) are specified, to configure electricity metering, the file number is specified in the "File#" field,  which stores power and power profiles.
16 16  
... ... @@ -84,7 +84,7 @@
84 84  
85 85  Viewing and changing the metering parameters in the memory of the metering device is carried out in accordance with the instructions of the operating manual for this device.
86 86  
87 -=== 2.2. Setting up metering channels ===
87 +== 2.2. Setting up metering channels ==
88 88  
89 89  Electricity meters often do not need to manually add channels to the list of tags, so all the settings are in the metering protocol.  The display of the used accounting channels from the protocol automatically appears on the **Tags, channels** tab, but with a ban on editing actions.
90 90  
... ... @@ -96,11 +96,11 @@
96 96  
97 97  The forms for filling in the fields for setting up electricity metering protocols are different and depend on the type/model of the device, instructions for working with the protocols can be described in different manuals and, if necessary, provided to the User.
98 98  
99 -== 3. ENERGY METERING (COMING) ==
99 += 3. ENERGY METERING (COMING) =
100 100  
101 -=== 3.1. Device Setup (Coming) ===
101 +== 3.1. Device Setup (Coming) ==
102 102  
103 -== 4. OTHER TYPES OF METERING ==
103 += 4. OTHER TYPES OF METERING =
104 104  
105 105  
106 106  In addition to metering electricity and energy resources, the CENTO software supports tracking of operating time, emissions and discharges, as well as product accounting.
... ... @@ -107,7 +107,7 @@
107 107  
108 108  Metering can be implemented not only on the basis of specialized metering devices, but also performed in the CENTO software itself on the basis of tags (real-time data). For example, using information about the state of the equipment (0 - disabled and 1- enabled), the user can set up a metering channel that will calculate the operating time of the equipment. And using the processing functions (see Section 5 of this manual), you can form metering channels (increments) from the current capacity, instantaneous flow or an ever-growing meter.
109 109  
110 -== 5. CALCULATED CHANNELS ==
110 += 5. CALCULATED CHANNELS =
111 111  
112 112  If the device installed at any connection does not have the function of storing interval values of electricity/power in the memory, as well as archived values for other types of metering, CENTO has the function of generating interval values from tags (real-time data). In order to create a metering channel, go to Settings > Devices, tags, channels > Calculation channels (see Fig. 5.1).
113 113  
... ... @@ -115,7 +115,7 @@
115 115  
116 116  Figure 5.1. List of calculated channels
117 117  
118 -=== 5.1. Channel from tag ===
118 +== 5.1. Channel from tag ==
119 119  
120 120  To create a new metering channel from real-time data (tags), click the button [[image:Screenshot 2025-11-30 at 16.28.39.png||height="18" width="92"]]
121 121  
... ... @@ -149,7 +149,7 @@
149 149  
150 150  Processing the calculated channel with formula input.
151 151  
152 -=== 5.2. Calculated channel ===
152 +== 5.2. Calculated channel ==
153 153  
154 154  To create a channel that processes the values of several connections, or interval values, for example, summing up electricity consumption by a group of consumers (total energy consumption) or calculating the balance of consumed energy, click the button on the **Calculated channels** tab (see Fig. 4.1), then click [[image:Screenshot 2025-11-30 at 16.33.58.png||height="22" width="116"]]
155 155  
... ... @@ -176,7 +176,7 @@
176 176  * rr_imp - R+ readings
177 177  * rr_exp - R- readings
178 178  
179 -=== 5.3.  Calculated channels via Information Model ===
179 +== 5.3.  Calculated channels via Information Model ==
180 180  
181 181  For calculation channels of the same type, it is possible to define custom formulas that operate based on Information Model objects and their attributes. In addition to tags and channels, the Information Model can also supply supplementary data (e.g., reference information). To create a template, click the create template button [[image:Screenshot 2025-11-30 at 16.36.34.png||height="27" width="26"]] as shown in Fig. 5.4.
182 182  
... ... @@ -210,7 +210,7 @@
210 210  
211 211   The braces **{ }** contain the arguments that need to be entered in the data entry fields as in Fig. 5.7.
212 212  
213 -=== 5.4. Downloading/Uploading calculated channels ===
213 +== 5.4. Downloading/Uploading calculated channels ==
214 214  
215 215  The** Downloading/Uploading configuration files** page (Settings > Configuration files) provides functionality for importing and exporting calculation metering channels using Excel files.
216 216  
... ... @@ -228,11 +228,11 @@
228 228  |integral|Integral of Values|Integral by tag ID40011100 in a 1-hour time interval
229 229  |first|Indication at the beginning of the interval|first([ti50206_type5], 3600, 0, 0) – calculation of readings based on the ID50206 tag at the beginning of the interval, calculated every hour
230 230  
231 -== 6. RECEIPT OF ACCOUNTING DATA ==
231 += 6. RECEIPT OF ACCOUNTING DATA =
232 232  
233 233  The** Analysis of the receipt of data** page is the same for all types of metering. It is described in details in the "User manual"
234 234  
235 -=== 6.1. Manual polling ===
235 +== 6.1. Manual polling ==
236 236  
237 237  If it is necessary to re-acquire data from metering devices, a manual poll should be performed. To do this, navigate to the **Receipt of metering data** page (Analysis > Receipt of metering data). This action opens the **Analysis of the receipt of data** interface (see Fig. 6.1)
238 238  
... ... @@ -254,7 +254,7 @@
254 254  
255 255  The **Refresh** button requeries the data from the database for the current view.
256 256  
257 -=== 6.2. Recalculation of calculated channels ===
257 +== 6.2. Recalculation of calculated channels ==
258 258  
259 259  In case of changes in the data used in the calculation channels or changes in the calculation formulas, it is necessary to recalculate the values of the calculated channels. This is performed in the **Analysis of the receipt of data** interface (Analysis > Receipt of metering data). The button [[image:Screenshot 2025-11-30 at 16.47.46.png||height="20" width="70"]] appears if the devices to which the calculated channels are bound are selected in the tree.
260 260  
... ... @@ -266,9 +266,9 @@
266 266  
267 267  At the end of the recalculation process, the information on the **Analysis of metering data** page (Analysis > Metering data) will be updated.
268 268  
269 -== 7. ANALYSIS OF METERING DATA ==
269 += 7. ANALYSIS OF METERING DATA =
270 270  
271 -=== 7.1. Viewing metering data ===
271 +== 7.1. Viewing metering data ==
272 272  
273 273  To view historical data on electricity/energy metering, select **Metering data** in the drop-down list of the **Analysis** menu. As a result, the** Analysis of data metering** page opens (see Fig 7.1 – Fig. 7.2).
274 274  
... ... @@ -282,7 +282,7 @@
282 282  
283 283  A more detailed description of this interface is described in the "User manual".
284 284  
285 -=== 7.2. Metering data manual entry ===
285 +== 7.2. Metering data manual entry ==
286 286  
287 287  With the appropriate rights, the User can make a manual entry of metering data. To do this, you hover the cursor over the desired cell in the table, perform a left click of the mouse and enter a new value, after which the save value icon appears on the right side of the input field [[image:Screenshot 2025-11-30 at 16.51.39.png]]. Press it or //Enter// on your keyboard, and the value goes to the CENTO database. For devices where only manual data entry is provided, CENTO has developed a procedure for filling the cells between two manual entries. If readings are recorded at 10:00 a.m. and then again at 8:00 p.m., the system automatically fills in the readings for all intermediate intervals. For electricity metering channels, the system additionally calculates and populates the corresponding energy and power values.
288 288